INFORMATION HUB

What Is Fire Compartmentation?

Fire compartmentation is the principle of dividing a building into separate areas, or compartments, that are designed to restrict the spread of fire and smoke. It is a cornerstone of building fire safety in the UK, supporting safe escape, protecting people who stay in place and helping firefighters. This guide explains what fire compartmentation is, how compartments are formed, what can undermine them and how to keep them effective.

Fire compartmentation explained

A fire compartment is a part of a building enclosed by fire-resisting construction, such as walls and floors, which is intended to contain a fire for a set period. If a fire starts in one compartment, the aim is to keep it there for long enough for people to escape or be evacuated, and to limit damage to the rest of the building.

Compartmentation also protects escape routes. Protected stairways and corridors are separated from the rest of the building with fire-resisting construction and fire doors, so that people can use them to reach a place of safety.

Why compartmentation is so important

Compartmentation supports the overall fire strategy for a building. In some residential buildings, the evacuation strategy relies heavily on compartmentation, with residents in flats not directly affected by a fire able to remain where they are unless told otherwise. That approach only works if each flat and the common parts are properly separated.

In commercial buildings, compartmentation can help limit the size of a fire, protect high-risk areas such as plant rooms and storage, and help keep escape routes usable for longer.

What makes up a fire compartment?

A compartment is only as strong as its weakest point. Walls, floors, junctions, doors and service penetrations all need to work together. The main components are:

  • Compartment walls and floors built to the fire resistance specified for the building.
  • Fire doors where people need to pass through compartment walls or into protected routes.
  • Fire stopping around pipes, cables, ducts and other penetrations, and at joints.
  • Fire dampers or fire-resisting ductwork where ventilation passes through a compartment line.
  • Cavity barriers in concealed spaces that could otherwise allow fire to bypass compartment lines.
  • Fire-resisting glazing where vision panels or screens form part of the construction.

How compartmentation requirements are set

For new buildings and material alterations in England, the Building Regulations 2010 apply, with Approved Document B providing guidance on how the fire safety requirements can be met. It covers where compartmentation is needed and the levels of fire resistance expected for different building types, heights and uses. Some projects follow alternative design codes such as BS 9999 or BS 9991, or a fire-engineered approach.

The fire strategy for a building should identify where compartment lines are and what performance they need. In existing buildings, the fire risk assessment required under the Regulatory Reform (Fire Safety) Order 2005 should consider whether compartmentation is being maintained.

Common threats to compartmentation

Compartmentation is frequently compromised after a building is completed. Typical problems include:

  • New services installed through walls and floors without the openings being sealed.
  • Fire doors propped open, damaged or fitted with unsuitable hardware.
  • Compartment walls that stop at a suspended ceiling instead of continuing to the slab above.
  • Missing or damaged cavity barriers in voids.
  • Gaps at the head of walls and around frames.
  • Unsuitable materials used to fill openings.

Many of these issues are hidden above ceilings, inside risers or behind panels, which is why compartmentation surveys often involve opening up and inspecting concealed areas.

Compartmentation surveys

A compartmentation survey looks at the fire-resisting construction in a building to identify breaches and defects. It typically involves reviewing drawings and the fire strategy where available, inspecting accessible voids and risers, recording defects with photographs and locations, and recommending remedial work. Surveys are often prompted by a fire risk assessment, a change of use, refurbishment or concerns about previous works.

Frequently asked questions

What is a compartment wall?

A compartment wall is a fire-resisting wall that separates one fire compartment from another. Its required fire resistance depends on the building and its fire strategy.

Does compartmentation apply to existing buildings?

Yes. Compartmentation installed when a building was constructed needs to be maintained, and those responsible for fire safety in existing premises should consider it as part of the fire risk assessment.

How do I know where the compartment lines are in my building?

Fire strategy drawings, building records and fire safety information handed over on completion may show compartment lines. Where records are missing, a competent professional can help establish them.

What happens if a compartmentation breach is found?

Breaches should be recorded and assessed, and suitable remedial work arranged using appropriate tested systems. Significant concerns may also need to be reflected in the fire risk assessment.

This guide is general information only. Compartmentation requirements depend on the individual building, so get building-specific advice from a competent professional.

Related guides

Concerned about compartmentation in your building? Lancashire Fire Security can discuss your building and help you work out the right next step. Email [email protected] or call 0800 038 9841.

Need advice on a passive fire protection project?

Tell us about your building, project or compliance question.

PASSIVE FIRE PROTECTION

Services | Knowledge Hub | About | Contact

Company Number: 11888399 | VAT Registration number: 373832577

0800 038 9841

© COPYRIGHT 2026 – LANCASHIRE FIRE & SECURITY LTD – ALL RIGHTS RESERVED