Common Fire-Stopping Defects

Fire stopping is designed to seal openings and joints in fire-resisting walls and floors. When it is missing, damaged or wrongly installed, fire and smoke may be able to pass through a compartment line much sooner than the building’s design intended. This guide describes the fire-stopping defects most commonly found in buildings, why they matter and how they can be avoided and put right.

Why fire-stopping defects are so common

Fire stopping is often installed late in a project, by different trades, in confined spaces that are then covered up. After completion, buildings are constantly changing: new cables, pipe replacements and IT upgrades all create openings. Without good control of works, defects accumulate over time and, because they are hidden in risers and voids, they can go unnoticed.

1. Open, unsealed penetrations

The most basic defect is an opening that has simply not been sealed. Holes made for services, or left oversized around them, may be found in risers, above ceilings and in plant rooms. Even small gaps can allow smoke and hot gases through.

2. Unsuitable materials

A frequent finding is an opening filled with materials that are not designed or tested for fire stopping, such as:

  • General-purpose expanding foam that is not fire rated.
  • Standard decorators’ or silicone sealants not tested for the application.
  • Loose mineral wool stuffed into gaps without a tested system.
  • Off-cuts of plasterboard, timber or other building materials.

These may look like a seal but are unlikely to provide the required fire performance.

3. Products used outside their tested scope

Fire-stopping products are tested in specific configurations. Problems arise when a product is used with a different type of pipe, a larger opening, a wall or floor type it was not tested in, or at the wrong depth. Mixing products from different manufacturers’ systems can also fall outside the test evidence.

4. Missing pipe collars and wraps

Plastic pipes soften and collapse in a fire, leaving an opening. Collars and wraps are designed to close this off as they expand. Missing, undersized or poorly fixed collars, or collars fitted on only one side where both sides are needed, are common defects.

5. Services added after the seal was installed

Cables are often pushed through existing batts or sealant without the seal being made good. Over time, a once-compliant seal may be riddled with holes and gaps.

6. Poor installation workmanship

  • Batts not cut neatly, leaving gaps at the edges.
  • Coatings not applied to the required thickness or over the full surface.
  • Sealant applied without the correct backing material or depth.
  • Services not supported as the manufacturer requires.

7. Head-of-wall and linear joint gaps

Gaps at the top of compartment walls, where they meet the slab, and at movement joints are easily missed. They need suitable joint seals that can accommodate any expected movement.

8. Walls that stop short

Sometimes a compartment wall stops at a suspended ceiling rather than continuing to the structure above, leaving the void open. This is a compartmentation defect rather than strictly a fire-stopping one, but it is often discovered at the same time.

9. No labelling or records

Missing labels, photographs and installation records do not stop a seal working, but they make it much harder to know what was installed, whether it is suitable and who did the work.

Preventing and remedying defects

Steps that can help include specifying tested systems, using competent and, where appropriate, third-party certified installers, controlling later works with permits, requiring photographic records and labels, and carrying out periodic inspection. When defects are found, remedial work should use suitable tested systems, be recorded and, where significant, be reflected in the fire risk assessment. Our inspection checklist can help with routine checks.

Frequently asked questions

How serious is a small gap around a cable?

Any unsealed opening in fire-resisting construction can reduce its performance. The significance depends on the location and building, so defects should be recorded and assessed by a competent person.

Can defective fire stopping be repaired rather than replaced?

Sometimes. Some systems can be made good with compatible products, but in other cases the seal needs to be removed and reinstalled. The manufacturer’s guidance and test evidence should be followed.

Who should carry out remedial fire stopping?

Remedial work should be carried out by competent installers familiar with the products used. Many clients choose installers who hold third-party certification.

How are hidden defects found?

Through inspection of risers, voids and ceiling spaces, which may involve lifting tiles, opening hatches or more intrusive investigation.

This guide is general information only. Whether a defect needs remedial work depends on the building and its fire strategy, so get building-specific advice from a competent professional.

Related guides

Investigating a possible fire-stopping defect? Lancashire Fire Security can discuss your building and help you identify the appropriate next step. Email [email protected] or call 0800 038 9841.

Need advice on a passive fire protection project?

Tell us about your building, project or compliance question.

PASSIVE FIRE PROTECTION

Services | Knowledge Hub | About | Contact

Company Number: 11888399 | VAT Registration number: 373832577

0800 038 9841

© COPYRIGHT 2026 – LANCASHIRE FIRE & SECURITY LTD – ALL RIGHTS RESERVED