Passive Fire Protection Inspection Checklist
Passive fire protection only works if it is in place and in good condition. Because much of it is hidden, problems can build up unnoticed, particularly after alterations and maintenance works. This checklist sets out practical points that building owners, facilities teams and managers can look out for during routine walk-rounds. It is not a substitute for a professional survey or a fire risk assessment, but it can help you spot issues and decide when to call in a competent person.
Before you start
- Gather what information you have: the fire risk assessment, fire strategy, drawings showing compartment lines and any fire safety information handed over on completion.
- Check previous inspection reports and records of fire-stopping or fire door work, including labels and photographs.
- Note any recent works by contractors, such as new cabling, pipework, IT or HVAC installations.
- Arrange safe access to risers, plant rooms and ceiling voids, and follow your site’s safety procedures.
Fire doors
- Is the door closed, or held open only by a suitable automatic release device?
- Does the self-closer shut the door fully into its frame from any open position, where one is fitted?
- Are intumescent and smoke seals present, intact and not painted over?
- Do the gaps around the leaf look even and not excessive?
- Are the hinges secure, with no missing screws?
- Is the leaf or frame damaged, or are there holes from removed hardware?
- Is any glazing intact, and does it appear to be the original fire-resisting type?
- Is the correct signage in place?
Fire stopping and service penetrations
- Are there open holes or gaps around pipes, cables, ducts or trays passing through walls and floors?
- Have new services been added through existing seals without the seal being reinstated?
- Are there signs of unsuitable materials, such as non-fire-rated expanding foam, general sealant or loose packing?
- Are pipe collars and wraps present on plastic pipes where you would expect them?
- Are batts, boards and sealants intact and undamaged?
- Are seals labelled, and do labels match your records?
Compartment walls and floors
- Do compartment walls continue up to the floor slab or roof above, rather than stopping at a suspended ceiling?
- Are there gaps at the head of walls or at junctions with other construction?
- Has any board or blockwork been damaged, cut or removed?
- Are access panels and hatches in fire-resisting construction suitably rated and closed?
Cavity barriers and concealed spaces
- In accessible ceiling voids and roof spaces, can you see cavity barriers where compartment lines run?
- Are barriers continuous, well fixed and not sagging or displaced?
- Are gaps around services passing through barriers sealed?
- Have barriers been disturbed or removed during works?
Ductwork and dampers
- Where ductwork crosses a compartment line, is there a fire damper or fire-resisting ductwork as expected?
- Is there evidence that fire dampers have been tested and maintained as required?
- Is the damper or duct properly sealed into the wall or floor?
Recording what you find
Good records are as important as the inspection itself. For each issue, note the location, what you observed and a photograph. Keep a log of defects and track remedial actions through to completion. Records support your fire risk assessment, help contractors understand the building and are increasingly expected as part of keeping accurate building information.
Controlling future works
Many defects are created by later works. Consider a permit-to-work system for any job that will breach a wall, floor or ceiling, with a requirement that openings are reinstated using suitable tested systems by a competent installer, and that work is recorded and signed off.
When to call in a professional
A walk-round can spot visible issues, but many problems are concealed and may need intrusive inspection. You should consider a professional survey if you find multiple defects, if records are missing, if the building has had significant alterations, or if your fire risk assessment recommends one.
Frequently asked questions
How often should I inspect passive fire protection?
It depends on the building’s risk, use and level of activity. Busy areas and fire doors may need more frequent checks. Some residential buildings have specific fire door checking duties under the Fire Safety (England) Regulations 2022.
Can I fix defects myself?
Minor issues like a propped-open door can be dealt with immediately, but repairs to fire stopping, fire doors and barriers should be carried out by competent people using suitable tested products.
Is this checklist enough to meet my legal duties?
No checklist can confirm compliance on its own. It is a practical aid that should sit alongside your fire risk assessment and professional advice.
This checklist is general information only. Every building is different, so get building-specific advice from a competent professional.
Related guides
Found something on your walk-round that concerns you? Lancashire Fire Security can discuss inspection and remedial support for your building. Email [email protected] or call 0800 038 9841.
Need advice on a passive fire protection project?
Tell us about your building, project or compliance question.
PASSIVE FIRE PROTECTION
Services | Knowledge Hub | About | Contact
Company Number: 11888399 | VAT Registration number: 373832577