Fire Doors and Their Role in Fire Safety
Fire doors are among the most visible parts of a building’s passive fire protection, and among the most frequently misused. A fire door that is wedged open, damaged or poorly maintained may offer little protection when it matters. This guide explains what fire doors do, how they work, what makes up a fire door assembly and how to keep them effective.
What does a fire door do?
A fire door has two jobs. In everyday use, it lets people pass through a fire-resisting wall. In a fire, when closed, it helps hold back fire and smoke for a period of time, protecting escape routes and helping to maintain compartmentation. Fire doors are commonly found on stairways, corridors, flat entrance doors, plant rooms, risers and other higher-risk areas.
Fire doors are part of the wider compartment line. If the door does not perform, the wall it sits in cannot perform either.
How fire doors are rated
Fire doors are tested as complete assemblies. In the UK, ratings are commonly expressed in one of two ways:
- FD ratings, such as FD30 or FD60, indicate the minutes of integrity achieved in testing to BS 476. An “S” suffix, as in FD30S, indicates the door also limits the passage of smoke.
- European classifications under BS EN 13501-2, such as E30 or EI30, based on testing to standards such as BS EN 1634-1. Smoke control may be shown with an additional classification.
The rating applies to the door as tested, including the leaf, frame, glazing, seals and hardware. Changing any component can affect performance, so replacements and modifications need to stay within the scope of the door’s evidence.
What makes up a fire door assembly?
- Door leaf – built to the tested specification, without unauthorised cut-outs or alterations.
- Frame – compatible with the leaf and securely fixed, with the gap between frame and wall suitably sealed.
- Intumescent seals – expand under heat to close the gap between leaf and frame.
- Smoke seals – where required, limit cold smoke getting past the door.
- Hinges – suitable for fire doors and fitted with the correct number of fixings.
- Self-closing device – closes the door fully from any open position, where a self-closer is required.
- Latches, locks and handles – compatible with the door’s evidence.
- Glazing – fire-resisting glass and glazing system where vision panels are fitted.
- Signage – such as “Fire door keep shut” where appropriate.
Installation matters
Even a well-made fire door can fail if it is badly installed. Gaps between the leaf and frame need to be within the tolerances set by the manufacturer, the frame must be properly fixed and the gap between the frame and surrounding wall should be sealed with a suitable tested product. Many manufacturers and certification schemes provide installation guidance, and BS 8214 gives a code of practice for timber-based fire door assemblies.
Common fire door problems
- Doors wedged or propped open.
- Self-closers missing, disconnected or not closing the door fully into the frame.
- Damaged, painted-over or missing intumescent and smoke seals.
- Excessive gaps around the leaf.
- Holes from removed hardware, letterboxes or spyholes that have not been suitably reinstated.
- Non-fire-rated glazing or replacement hardware.
- Damage to the leaf or frame.
Fire doors and the law in England
Under the Regulatory Reform (Fire Safety) Order 2005, fire doors in premises it covers are part of the fire safety measures that the responsible person must maintain. The Fire Safety Act 2021 clarified that, in multi-occupied residential buildings, the Order applies to flat entrance doors that open onto common parts. The Fire Safety (England) Regulations 2022 introduced specific fire door checking duties for responsible persons in certain multi-occupied residential buildings, along with duties to give residents information about fire doors. Our regulations guide explains the wider framework.
Frequently asked questions
Can fire doors be held open?
Some fire doors can be held open by devices that release the door automatically when the fire alarm operates, where this is appropriate for the building. Wedges and other improvised methods should not be used.
Can I fit new hardware to a fire door?
Only hardware that is compatible with the door’s test evidence or certification should be fitted. Unsuitable hardware or extra cut-outs can reduce the door’s fire performance.
How often should fire doors be checked?
Frequency depends on the building, its use and any specific legal duties that apply. Doors in busy areas are likely to need more frequent checks. Your fire risk assessment should help inform this.
How can I tell if a door is a fire door?
Many certified fire doors carry a label or plug on the edge of the leaf identifying the manufacturer or certification scheme. Where there is no evidence, a competent professional can help assess the door.
This guide is general information only. Fire door requirements vary between buildings, so get building-specific advice from a competent professional.
Related guides
- What Is Fire Compartmentation?
- Passive Fire Protection Inspection Checklist
- Passive Fire Protection Regulations in England
Have a question about the fire doors in your building? Lancashire Fire Security can discuss your requirements and help you decide on the next step. Email [email protected] or call 0800 038 9841.
Need advice on a passive fire protection project?
Tell us about your building, project or compliance question.
PASSIVE FIRE PROTECTION
Services | Knowledge Hub | About | Contact
Company Number: 11888399 | VAT Registration number: 373832577